Galaxy VS UPS GVSUPS80K0B5HS
GVSUPS80K0B5HS
Modular three-phase UPS for data centres and business-critical loads. Account for battery configuration, expandable capacity and commissioning requirements in the electrical design.
- Rated power
- 80 kVA / 80 kW
- Output voltage
- 400 V AC 3 phases · 380 V AC 3 phases · 415 V AC 3 phases
- Battery type
- Lead-acid internal sold separately · Internal modular battery · VRLA
Product overview
Model GVSUPS80K0B5HS is rated at 80 kVA apparent power and 80 kW real power.
Published output voltage: 400 V AC 3 phases · 380 V AC 3 phases · 415 V AC 3 phases.
Battery configuration: Lead-acid internal sold separately · Internal modular battery · VRLA.
Runtime depends on the load and battery configuration. Input supply, earthing, battery and installation requirements must be checked before ordering. Manufacturer service and warranty statements are not a supply commitment by HRSCO; final terms are stated in our quotation.
Technical specifications
Main
| Main input voltage | 400 V AC 3 phases · 380 V AC 3 phases · 415 V AC 3 phases |
|---|---|
| Other input voltage | 380 V · 415 V |
| Maximum input current | 144 A |
| Max short time withstand current | 65 kA |
| Input harmonic distortion | Less than 3 % for full load |
| Load power factor | From 0.7 leading to 0.7 lagging without any derating |
| Cos phi | 0.99 |
| Manufacturer voltage / load data | 340...460 V 400 V |
| Input frequency | 40...70 Hz |
| Output voltage | 400 V AC 3 phases · 380 V AC 3 phases · 415 V AC 3 phases |
| Other output voltage | 380 V · 415 V |
| Rated power in W | 80 kW |
| Rated power in VA | 80 kVA |
| Bypass type | Built-in static bypass |
| Crest factor | 2.5 |
| Harmonic distortion | Less than 3 % |
| Maximum configurable power in VA | 80 kVA |
| Maximum configurable power in W | 80 kW |
| Output harmonic distortion | < 1% linear load and < 3% non-linear load |
| Output overload operation | 10 minutes at 125% and 60 seconds at 150% |
| Output voltage tolerance | +/- 5% after 2ms · +/-1% after 50ms |
| Waveform type | Sine wave |
| Output frequency | 50 Hz sync to mains · 60 Hz sync to mains |
Complementary
| Max current discharge | 217 A |
|---|---|
| Battery type | Lead-acid internal sold separately |
| Control panel | Touch screen LCD user interface |
| UPS connectivity | Embedded network management card 4 |
| Color | White |
| Height | 197 cm |
| Width | 55 cm |
| Depth | 84.7 cm |
| Product weight | 296 kg |
| USB compatible | No |
| Provided equipment | Dust filter · Installation manual · Integrated network management · Start-up service · EcoStruxure Ready |
| Redundant | No |
| Range of product | Galaxy VS |
| Product or component type | Uninterruptible power supply (UPS) |
Environment
| Standard | IEC 62040-1-1 · IEC 62040-2 · OSHPD |
|---|---|
| Ambient air temperature for operation | 0…40 °C |
| Ambient air temperature for storage | -15…40 °C |
| Storage altitude | 0…3048 m |
| IP protection | IP20 |
| Relative humidity | 0…95 % non-condensing |
| Storage relative humidity | 10…80 % non-condensing |
| Acoustic level | 65 dBA |
| Heat dissipation | 9263 Btu/h |
| Operating altitude | 0...3300 ft |
Batteries & Runtime
| Battery type | Internal modular battery · VRLA |
|---|---|
| Battery voltage | 480 V |
| Extendable runtime | 0 |
| Discharge battery voltage | 384 V |
Packing Units
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 208.2 cm |
| Package 1 Width | 101 cm |
| Package 1 Length | 75.5 cm |
| Package 1 Weight | 250 kg |
Contractual warranty
| Warranty (in months) | 12 |
|---|